Compatible with lead-acid and lithium-ion batteries;
Support diesel generator input source;
IP65 protection, low noise < 35dB;
Battery reverse connection protection,anti-power control function
Input power source priority can be set by users;
Support full power discharge, automatic management of battery charge and discharge;
Model | R12KH3 |
Input (PV) | |
Max. power(KW) | 15,6 |
Max. DC voltage(V) | 1000 |
MPPT voltage range(V) | 180~850 |
Max.input current of single MPPT(A) | 12,5 |
MPPT tracker/strings | 2//1 |
AC output | |
Rated output power(kVA) | 13,2 |
Max. output current(A) | 19,1 |
Grid voltage/range(V) | 400/360~440 |
Frequency (Hz) | 50/60 |
PF | 0.8lagging-0.8leading |
THDi | <3% |
AC output topology | 3W+N+PE |
Battery | |
Battery voltage range(V) | 125~600 |
Max. charging voltage(V) | 600 |
Full battery voltage(V) | 250 |
Max. charge/discharge current(A) | 50 |
Battery type | lithium /Lead-acid |
Communication interface | CAN/RS485 |
EPS output | |
Rated power (kVA) | 13,2 |
Rated output voltage(V) | 400 |
Rated output current(A) | 19,1 |
Rated frequency (Hz) | 50/60 |
Automatic switching time (ms) | <20 |
THDu | <2% |
Overload capacity | 110%, 30S/120%, 10S/150%, 0.02S |
General data | |
Battery chage/dischage efficiency | 96,80% |
DC Max. efficiency | 98,20% |
Europe efficiency | 97,50% |
MPPT efficiency | 99,50% |
Ingress protection | IP65 |
Noise emission (dB) | <35 |
Operation temperature | - 25℃~ 60℃ |
Cooling | Natural |
Relative humidity | 0 ~95%(non-condensing) |
Altitude | 2,000m(>2,000 Derating) |
Dimensions W*D*H (mm) | 550*200*515 |
Weight (kg) | 25 |
Isolation transformer | No |
Self-consumption(W) | <3 |
Display and communication | |
Display | LCD |
Interface:RS485/Wifi/4G/ CAN/DRM | Yes/ Opt/ Opt/ Yes/ Yes |
Certificates | CE、TUV、SAA、NRS |